Room Integrity Testing

Room Integrity Testing

Without releasing the actual suppression system agent into the protected area, an integrity test forecasts how long fire suppressant agents will take to descend to a specific level in the room.

The gateway is where the system is put up. After the protected area is pressurized and fan flow readings are obtained, the room is depressurized to get measurements for comparison.

The predicted retention time is calculated from the leakage characteristics and the enclosure and extinguishing system data. A retention time of 10 minutes is the normal minimum period the suppressant agents except C02 total flood systams that requires a 20min retention Time.

Ten minutes is long enough for most deep-seated fires to be cooled so that re-ignition is unlikely.

Gaseous fire suppression systems should provide adequate time for the emergency services to attend and in most cases prevent the fire taking hold.